网站转让
  • 网站首页
  • 关于我们
  • 产品中心
  • 荣誉资质
  • 新闻中心
  • 联系我们
当前位置:网站首页 > 新闻动态
零序电流互感器保护原理
添加时间:2018/6/15 14:39:54     浏览次数:
零序电流互感器保护原理
Protection principle of zero sequence current transformer
零序电流保护具体应用可在三相线路上各装一个电流互感器(CT),或让三相导线一起穿过一零序CT,也可在中性线N上安装一个零序CT,利用这些C.T来检测三相的电流矢量和,即零序电流Io,IA+IB+IC=Io,当线路上所接的三相负荷完全平衡时(无接地故障,且不考虑线路、电器设备的泄漏电流),Io=0;当线路上所接的三相负荷不平衡,则Io=IN,此时的零序电流为不平衡电流IN;当某一相发生接地故障时,必然产生一个单相接地故障电流Id,此时检测到的零序电流IO=IN+Id,是三相不平衡电流与单相接地电流的矢量和。
Zero sequence current protection can be applied to a three-phase line with a current transformer (CT), or a three-phase wire through one zero sequence CT together, or a zero sequence CT on the neutral line N, using these C.T to detect the three-phase current vector and the zero sequence current Io, IA+IB+ IC=Io, when the three-phase load connected to the line is finished. Full balance (without grounding fault, without considering leakage current of circuit and electrical equipment), Io=0; when the three-phase load on the line is unbalanced, then Io=IN, the zero sequence current of this time is unbalance current IN; when a phase occurs grounding fault, a single-phase grounding fault current Id, at this time the detected zero The sequence current IO=IN+Id is the vector sum of the three-phase unbalanced current and the single-phase earth current.
上一页  零序电流互感器保护原理  
下一页  一次消谐装置
  • 版权@网站转让
  • 技术支持:保定遨游公司
  • 一键拨号
  • 产品中心
  • 联系我们